M12 interface, IO-Link Hub, PNP, 16DI/DO configurable, standard module, 00BG01

M12 interface, IO-Link Hub, PNP, 16DI/DO configurable, standard module, 00BG01

Order code: 00BG01
Order number: FNI IOL-309-S01-M12
  • IO-Link M12 Hub 16×DI PNP(Figure 1)
  • IO-Link device
  • 8 Signals from port 16
  • Input/output configurable
  • Protection Class IP67 (when properly connected)
收藏 询盘

Relevant recommendation

  • Functional parameter
  • Resource download
  • Related accessory
IO-Link设备
说明Standard module
类型16×DI/DO PNP
Rated working voltage UB18...30 V  
IO-Link RUN Indicates the co-function indicatorGreen LED indicator
Power start indicatorGreen LED indicator
Connection: IO-Link portM12,A-coded, male
Connection: I/O portM12, A-coded, female
Connecting UOThrough the IO-Link interface
Connecting UA通过IO-Link接口
Number of I/O ports8
Input quantity最大16
Output quantity最大16
Can be configured
Single channel monitoring
It can be encoded through IO-Link
Maximum load current, sensor/channel100 mA
Maximum load current actuator0.5A
Port status indicatorYellow/Red LED
Total current UT< 1.4A
Total current UO< 1.4A
Protection level in accordance with IEC 60529IP 67 (when properly connected)
Operating temperature-25...+70 ℃
Storage temperature-25...+85 °C
fastener2 mounting holes
Dimensions (L × W × H)153.4×65×29 mm
Shell materialZinc alloy
备注-
lO-Link1.1
Maximum cycle4 ms
IO-Link processes data length2 input bytes /2 output bytes
Indicator light communicationGreen LED indicator
Indicator light errorRed LED indicator


specification

  • 00BG01 (FNI IOL-309-S01-M12) - Specification

    2024-07-31   634.72KB

Operation manual

  • 00BG01 (FNI IOL-309-S01-M12) - Instructions

    2024-09-30   930.29KB

EPLAN

  • 00BG01 (FNI IOL-309-S01-M12) -EPLAN (Electrical drawing)

    2024-09-20   993.15KB

2D digital module

  • 00BG01 (FNI IOL-309-S01-M12) -2D (DWG file)

    2024-07-05   699.86KB

3D digital module

  • 00BG01 (FNI IOL-309-S01-M12) -3D (STEP file)

    2024-07-05   1.63MB
" class="hidden">汉朝百科